Sizing Up A Condensate Unit

Sizing Up A Condensate Unit

SELECTION TABLE (EDR RATING)

Use this formula to determine the EDR rating
  • EDR equals boiler H.P. x 140
  • EDR equals BTU per hour divided by 250
  • EDR equals lbs. of steam per hour x 4
 
CAPACITY CAPACITY MODEL CLASS RECEIVER RECEIVER NUMBER OF PORTS
EDR G.P.M. DISH P.S.I. H.P. DISH SIZE R.P.M. SIZE (GALLONS) PORT SIZE RETURN SIDE
1,000 1 1/2 10 20 30 40 1/2 1/2 1/2 3/4 1″ 1″ 1″ 1″ 3500 H 10 SIMPLER OR 20 DUPLEX 2″ 2″ 2 2
2,000 3 10 20 30 40 50 1/2 1/2 1/2 3/4 1 1/2 1″ 1″ 1″ 1″ 1″ 3500 H 10 SIMPLER OR 20 DUPLEX 2″ 2″ 2 2
4,000 6 10 20 30 40 50 1/2 1/2 1/2 3/4 1 1/2 1″ 1″ 1″ 1″ 1″ 3500 H 10S OR 20D 2″ 2″ 2 2
6,000 9 10 20 30 40 50 1/2 1/2 1/2 3/4 1 1/2 1″ 1″ 1″ 1″ 1″ 3500 H 20D OR 40D 2″ 3″ 2 2
10,000 15 10 20 30 40 50 1/2 1/2 1/2 1 2 1″ 1″ 1″ 1″ 1 1/2″ 3500 H 20D OR 40D 2″ 3″ 2 2
20,000 30 10 20 30 40 50 1/2 1/4 1 1 1/2 2 1″ 1″ 1″ 1″ 1 1/2″ 3500 H 65D 3″ 2
25,000 37 1/2 10 20 30 40 50 3/4 1 1 1/2 1 1/2 2 1/2 1″ 1″ 1″ 1″ 1 1/2″ 3500 H 65D 3″ 2
30,000 45 10 20 30 40 50 3/4 1 1 1/2 2 1/2 5 1″ 1″ 1″ 1 1/2″ 1 1/2″ 3500 H 65D 3″ 2
40,000 60 10 20 30 40 50 1 1/2 1 1/2 2 5 5 1″ 1″ 1 1/2″ 1 1/2″ 1 1/2″ 3500 H 65D 3″ 2
50,000 75 10 20 30 40 50 2 2 3 5 7 1/2 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 3500 H 65D 3″ 2
65,000 97 1/2 10 20 30 40 50 60 2 2 1/2 2 1/2 5 7 1/2 7 1/2 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 3500 M 110D 4″ 2
80,000 120 10 20 30 40 50 60 2 1/2 2 1/2 2 1/2 5 7 1/2 7 1/2 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 3500 M 110D 4″ 2
100,000 150 10 20 30 40 50 60 3 3 3 5 7 1/2 10 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 3500 H 110D 4″ 2
  • M = Medium Head Pumps
  • H = High Head Pumps
  • TFC MOTORS ARE STANDARD 3 THRU 10 H.P. AT NO EXTRA CHARGE